Water Contaminants

Water Contaminants
Microbiological Contaminants MCL PHG (MCLG) CSUF Average Range of Detection’s Sample Date Violation Typical Source of Contaminant
Total Coliform Bacteria 5% of Monthly Pos Samples 0 0 1 of 40 2025 No Naturally present in the environment
Radioactive Contaminants
Gross Alpha Particle (pCi/l) 15 0 ND ND 2024 No Erosion of natural deposits
Inorganic Contaminants
Arsenic (ug/l) 10 0.004 2.1 ND to 4.1 2024 No Erosion of natural deposits
Barium (mg/l) 1000 0 92 82 to 100 2024 No Erosion of natural deposits
Nitrate as NO3 (mg/l) 10 10 2.12 0.72 to 4.7 2025 No Runoff and leaching from fertilizer use; leaching from septic tanks and sewage; erosion of natural deposits
Synthetic Organic Contaminants
1,2,3-TCP 0.005 0.0007 ND ND 2024 No* Discharge from industrial and agricultural chemical factors; leaching from hazardous waste sites; used as cleaning and maintenance solvent, paint and varnish remover, and cleaning and degreasing agent; byproduct during the production of other compounds and pesticides.
Disinfectant Residuals
Chlorine (ppm) 4.0 4.0 1.35 0.38 to 2.00 2025 No Drinking water disinfection
Lead and Copper
Contaminant AL MCLG CSUF 90th Percentile Sites Above AL Sample Date Violation Typical Source of Contaminant
Lead (ug/l) 15 0.2 0.005 None 2023 No Internal corrosion of household plumbing systems.
Copper (mg/l) 1.3 0.17 0.26 None 2023 No Internal corrosion of household plumbing systems.

About Nitrate: Nitrate in drinking water in levels above 10 mg/l is a health risk for infants less than six months of age. High nitrate levels in drinking water can interfere with the capacity of the infant’s blood to carry oxygen, resulting in serious illness; symptoms include shortness of breath and blueness of the skin. High nitrate levels may also affect the ability of the blood to carry oxygen in other individuals, such as pregnant women and those with certain specific enzyme deficiencies. Nitrate levels, may rise quickly for short periods of time because of rainfall or agricultural activity. If you are caring for an infant, you should ask advice from your health care provider, or choose to use bottled water for mixing formula and juice for your baby. If you are pregnant, you should drink bottled water.

About Lead: If present, elevated levels of lead can cause serious health problems, especially for pregnant women and young children. Lead in drinking water is primarily from materials and components associated with service lines and home plumbing. Fresno State University is responsible for providing high quality drinking water, but cannot control the variety of materials used in plumbing components. When your water has been sitting for several hours, you can minimize the potential for lead exposure by flushing your tap for 30 seconds to 2 minutes before using water for drinking or cooking. If you are concerned about lead in your water, you may wish to have your water tested. Information on lead in drinking water, testing methods, and steps you can take to minimize exposure is available from the Safe Drinking Water Hotline at 1-800-426-4791 or at http://www.epa.gov/safewater/lead.

About 1,2,3-TCP: Some people who drink water containing 1,2,3-trichloropropane in excess of the MCL over many years may have an increased risk of getting cancer.

Note Asterisk *: Contaminate source has been placed on “Standby” status. This source is no longer being used to provide domestic potable water to the distribution system and is only to be used in the event of an emergency for a short-term only.

Secondary and Unregulated Contaminants
Constituent Secondary MCL CSUF Average Range of Detection’s Sample Date Violation Typical Source of Contaminant
Total dissolved solids (mg/l) 1,500 230 190 to 310 2024 No Runoff/leaching from natural deposits
Specific Conductance 2,200 333 260 to 480 2024 No Substances that form ions when in water.
Chloride (mg/l) 600 19.2 6.5 to 44 2024 No Runoff/leaching from natural deposits.
Sulfate (mg/l) 600 7.1 3.5 to 14 2024 No Runoff/leaching from natural deposits.
Unregulated Contaminants   CSUF Average Range of Detection’s Sample Date    
Hardness (as CaCO3) (mg/l)   110 84 to 160 2024    
Calcium (mg/l)   25 20 to 35 2024    
Potassium (mg/l)   1.2 ND to 3.7 2024    
Sodium (mg/l)   23 21 to 24 2024    

Download the PDF